首页 | 本学科首页   官方微博 | 高级检索  
     

三维脉动热管耦合相变材料的传热与节能特性研究
引用本文:张志远,凌云志,崔奇,高恩元,张小松. 三维脉动热管耦合相变材料的传热与节能特性研究[J]. 制冷学报, 2022, 43(1): 131-137
作者姓名:张志远  凌云志  崔奇  高恩元  张小松
作者单位:东南大学能源与环境学院;中国矿业大学力学与土木工程学院
基金项目:国家自然科学基金(51876034),江苏省重点研发计划(BE2018118)资助项目。
摘    要:为研究三维脉动热管与相变材料耦合系统的传热与节能特性,本文搭建了三维脉动热管/相变材料耦合模块实验台,使用甲醇、乙醇和丙酮3种工质对充液率为34%、44%的三维脉动热管进行研究,建立了耦合模块的热阻模型,定义了耦合模块的热阻变化率;研究了在变送风温度(3~9 m/s)和速度(20~26℃)条件下耦合模块的热阻变化规律和...

关 键 词:数据中心冷却  三维脉动热管  相变材料  热阻
收稿时间:2021-06-21
修稿时间:2021-10-12

Heat Transfer and Energy Saving Characteristics of 3D Pulsating Heat Pipe Coupled with Phase Change Materials
Zhang Zhiyuan,Ling Yunzhi,Cui Qi,Gao Enyuan,Zhang Xiaosong. Heat Transfer and Energy Saving Characteristics of 3D Pulsating Heat Pipe Coupled with Phase Change Materials[J]. Journal of Refrigeration, 2022, 43(1): 131-137
Authors:Zhang Zhiyuan  Ling Yunzhi  Cui Qi  Gao Enyuan  Zhang Xiaosong
Affiliation:School of Energy and Environment, Southeast University;School of Mechanics and Civil Engineering, China University of Mining and Technology
Abstract:3D pulsating heat pipes and phase change materials(PCMs)can be used for energy-efficient data centers.In this study an experimental bench of a 3D pulsating heat pipe/PCM module was built to study the heat transfer and energy saving characteristics of the coupled system.The 3D pulsating heat pipe with two liquid-filling rates of 34%and 44%was studied using three working materials,methanol,ethanol,and acetone.The thermal resistance model of the coupling module was established,and the thermal resistance variation rate of the coupling module was defined.The thermal resistance variation and energy-saving characteristics of the coupling module were studied under conditions of variable air temperature(20-26℃)and velocity(3-9 m/s).In addition,the thermal resistance and energy-saving characteristics of the coupling module were studied.The results show that the thermal resistance change rate of the coupling module with 34%liquid filling rate is higher than that of the liquid filling rate of 44%,in which the thermal resistance change rates using methanol at 80 W and 120 W heating power are 48.2%and 48.7%,respectively.These are higher than those using ethanol and acetone under the same conditions.Compared with the traditional cooling method of data centers,the fans and chips can save 143.61 kW·h and 176.82 kW·h per year under 80 W heating power,respectively.
Keywords:data center cooling   3D pulsating heat pipe   phase change material   thermal resistance
本文献已被 维普 等数据库收录!
点击此处可从《制冷学报》浏览原始摘要信息
点击此处可从《制冷学报》下载免费的PDF全文
设为首页 | 免责声明 | 关于勤云 | 加入收藏

Copyright©北京勤云科技发展有限公司  京ICP备09084417号