调度中心SCADA与WAMS实时数据的差异
引用本文:齐文斌,肖晓春,李东平,徐兴伟,邵广惠. 调度中心SCADA与WAMS实时数据的差异[J]. 南方电网技术, 2013, 7(5): 87-91
作者姓名:齐文斌  肖晓春  李东平  徐兴伟  邵广惠
作者单位:北京四方继保自动化股份有限公司,北京100085;北京四方继保自动化股份有限公司,北京100085;内蒙古达拉特电厂,内蒙古 达拉特旗017000;东北电力调度通信中心,沈阳110180;东北电力调度通信中心,沈阳110180
摘    要:通过电网调度中心实时数据在线统计,比较了RTU与PMU曲线的相似程度和实时差异,发现在同一物理测点,直采RTU与PMU数据延迟小于1s;RTU与PMU的有功、电流幅值、电压幅值差异小于2%者居多,RTU与PMU的无功差异一般在5%~40%之间。分析显示,在电力系统分析计算中可以直接使用PMU的电流、电压瞬时量和有功量测数据;但应避免直接使用PMU电流、电压的相角信息和有选择地使用PMU的无功量测数据。建议通过定期检定来修正PMU角度补偿参数来提高相量测量的精度。

关 键 词:电力系统  PMU  SCADA  WAMS  数据质量  角度误差  无功功率

The Difference Between SCADA and WAMS Real Time Data in Dispatching Center
QI Wenbin,XIAO Xiaochun,LI Dongping,XU Xingwei and SHAO Guanghui. The Difference Between SCADA and WAMS Real Time Data in Dispatching Center[J]. Southern Power System Technology, 2013, 7(5): 87-91
Authors:QI Wenbin  XIAO Xiaochun  LI Dongping  XU Xingwei  SHAO Guanghui
Affiliation:1. Beijing Sifang Automation Co. , Ltd. , Beijing 100085, China; 2. Northeast China Electric Power Dispatch Center, Shenyang 110180, China; 3. Dalate Power Plant, Dalate, Inner Mongolia Autonomous Region 017000, China)
Abstract:With the online real-time statistical data from the dispatching centers of power system, the similarity and real-time differ-ence between RTU and PMU measurements are compared in this paper, and it is found that the data of RTU and PMU from straight telemetered measurements at a physical site are in difference with 1 s of time delay; the differences of active power, current magni- tude and voltage magnitude between PMU and RTU are generally less than 2% ; but that of reactive power between the two devices u- sually range from 5 %-40%. The analysis shows that in the calculation of power system, the measurement data of active power, cur-rent magnitude and voltage magnitude from PMU can be used directly, but that of current angle and voltage angle should not be used directly while that of reactive power should be used selectively. It is proposed to improve the accuracy of PMU phase angle measure-ments through periodically checking and adjusting of the phase angle compensation parameters.
Keywords:power system   PMU   SCADA   WAMS   data quality   angle error   reactive power