Abstract: | In designing a gas‐insulated bus (GIB) using N2/SF6 mixtures, there are many application problems, such as the mixture pressure needed in order to maintain the required dielectric and heat transfer performance. Problems of recycling SF6 are also essential in applying N2/SF6 mixtures. This paper presents the minimum breakdown field strength at lightning impulse and the temperature rise of the conductor and enclosure as measured for N2/SF6 mixtures. Considering the dielectric and heat transfer properties, we clarify the problems of application of mixtures to a GIB and discuss the appropriate mixture ratio of SF6 in designing a GIB comparable to the present dimensions. In addition, the lowest limit of SF6 content in a liquefied recovering method is theoretically estimated for reference in practical SF6 recovery from mixtures. It is important for design to consider both breakdown phenomena, including the area effect of electrode, and the heat transfer properties of mixtures. © 2001 Scripta Technica, Electr Eng Jpn, 137(4): 25–31, 2001 |