The potential for heat pumps in drying and dehumidification systems II: An experimental assessment of the heat pump characteristics of a heat pump dehumidification system using R114 |
| |
Authors: | K W Tai R Zylla S Devotta P J Diggory F A Watson F A Holland |
| |
Abstract: | An experimental heat pump dehumidifier is described. Actual coefficients of performance (COP)A are plotted against the gross temperature lift (TCO - TEV) for various bypass ratios and air velocities. Interpolated values of (COP)A for a specified temperature lift were obtained by fitting each set for various dry bulb temperatures of air leaving the humidifier using a linear equation. These values of (COP)A are plotted against the linear velocity of the air stream approaching the evaporator at different dry bulb temperatures. The curves show a maximum of (COP)A at approach velocities in the region of 1·6 ms?1. |
| |
Keywords: | Dehumidification Drying Heat energy and recycling Heat pump |
|