小电流接地系统单相接地故障选线新方法
引用本文:唐捷,周湶,伏进,孙才新,包中福. 小电流接地系统单相接地故障选线新方法[J]. 高电压技术, 2007, 33(12): 143-147
作者姓名:唐捷  周湶  伏进  孙才新  包中福
作者单位:重庆大学输配电装备及系统安全与新技术国家重点实验室,重庆400030;国家电网公司重庆市电力公司杨家坪供电局,重庆400050;重庆大学输配电装备及系统安全与新技术国家重点实验室,重庆,400030;国家电网公司四川省电力公司达州电业局,达州,635000
基金项目:重庆市科技计划重大项目(2004CA6003)。~~
摘    要:为改进小电流接地系统单相接地故障选线方法,结合数字信号处理中的相关分析技术与小波包分解技术,利用db小波包以适当频带宽度分解了这种故障后的暂态零序电流,自适应地选出各条线路上故障能量最大的特征频段。两两相关分析各线路故障特征频段对应小波包分解系数的波形,获得相关矩阵,并求出各线路的综合相关系数,最终给出按接地故障发生可能性大小排列的选线结果。理论分析及大量MATLAB仿真结果表明:该法不受故障条件的影响,可准确、可靠地实现配电网单相接地故障选线,适于中性点不接地或经消弧线圈接地系统。

关 键 词:小电流接地系统  故障选线  小波包  特征频段  相关分析
文章编号:1003-6520(2007)12-0143-05
收稿时间:2006-11-16
修稿时间:2006-11-16

New Method for Line Fault-detection Under Single-phase-to-earth Fault of Low Current Neutral Grounding Power System
TANG Jie,ZHOU Quan,FU Jin,SUN Cai-xin,BAO Zhong-fu. New Method for Line Fault-detection Under Single-phase-to-earth Fault of Low Current Neutral Grounding Power System[J]. High Voltage Engineering, 2007, 33(12): 143-147
Authors:TANG Jie  ZHOU Quan  FU Jin  SUN Cai-xin  BAO Zhong-fu
Affiliation:1.State Key Laboratory of Safety and New Technology of Power Transmission & Distribution Equipment and System,Chongqing University,Chongqing 400030,China;2.Yangjiaping Power Supply Bureau,Chongqing Electric Power Corporation,Chongqing 400050,China;3.Dazhou Power Corporation,Sichuan Electric Power Corporation State Grid Corporation,Dazhou 635000,China)
Abstract:An improved line fault-detection method is proposed in this paper by applying both the wavelet packets technology and the correlation analysis technology of digital signal processing.Firstly,each line's transient zero sequence current,which appears in the low current neutral grounding power system while a single-phase-to-earth fault occurring,is decomposed to obtain the suitable outputs of specific frequency bands.And the characteristic frequency band of each line,of which the transient capacitive current is most concentrated,is chosen adaptively according to the view of maximum energy.Secondly, the correlation analysis between each line's waveform of wavelet packets decomposition coefficient corresponding to its characteristic frequency band is carried out,so as to acquire the correlation matrix and then get each line's integrated correlation coefficient.Finally,the result of line fault-detection is obtained,which is arranged by the size of the probabilities of the grounding fault. The theoretical analysis and MATLAB simulations show that the proposed method can choose the faulty line exactly and reliably under all kinds of fault conditions.This method is suitable for both neutral insulated power networks and Peterson coil earthed power networks.
Keywords:low current neutral grounding power system  faulty line detection  wavelet packets  characteristic frequency band  correlation analysis