首页 | 本学科首页   官方微博 | 高级检索  
     

110kV新赛线高频通道衰耗过大问题的分析及处理
引用本文:褚国伟.110kV新赛线高频通道衰耗过大问题的分析及处理[J].江苏电机工程,2008,27(4):32-34.
作者姓名:褚国伟
作者单位:常州供电公司,江苏,常州,213000
摘    要:高频通道的可靠性对高频保护的正确动作起决定作用。针对常州电网110kV新赛线高频通道衰耗过大的问题进行分析,测试了高频通道上的电器设备工作性能,并分析了地返波干扰因素。通过对新赛线高频通道进行扫频试验,选择适合该高频通道的工作频率,有效地减小了该高频通道的衰耗。

关 键 词:高频通道  衰耗  工作频率  扫频试验

Analysis and Treatment for Oversize Attenuation Problem of 110 kV Xinsai Line High-frequency Channel
CHU Guo-wei.Analysis and Treatment for Oversize Attenuation Problem of 110 kV Xinsai Line High-frequency Channel[J].Jiangsu Electrical Engineering,2008,27(4):32-34.
Authors:CHU Guo-wei
Affiliation:CHU Guo-wei (Changzhou Power Company, Changzhou 213000, China)
Abstract:The reliability of high-frequency channel plays a decisive role in correct operation of carrier current protection.Aiming at oversize attenuation problem of 110 kV Xinsai line high-frequency channel,the work capability of wiring in high-frequency channel is checked,and interference factors of ground backward-wave are analyzed.Fitting operating frequency of Xinsai line high-frequency channel is decided through sweep checking of the channel.As a result,the attenuation of high-frequency channel is decreased effectively.
Keywords:high-frequency channel  attenuation  operating frequency  sweep check