对6kV供电系统内部过电压的分析及防范措施 |
| |
引用本文: | 霍现军.对6kV供电系统内部过电压的分析及防范措施[J].江苏电器,2008(4):41-44. |
| |
作者姓名: | 霍现军 |
| |
作者单位: | 电能(北京)产品认证中心有限公司,北京,100011 |
| |
摘 要: | 在6kv供电系统中,针对因电感负荷产生的操作过电压和单相接地产生的接地过电压,采取在电压互感器上加装一、二次消谐装置,在6kV母线上加装智能型接地补偿装置,在电动机和变压器侧加装过电压保护器的措施,是较好的消除过电压对供电系统威胁的有效方法。
|
关 键 词: | 6 kV供电系统 过电压 消谐器 接地补偿 |
文章编号: | 1007-3175(2008)04-0041-04 |
修稿时间: | 2007年9月21日 |
Analysis and Prevention Measures for Internal Over-Voltage of 6 kV Power Supply System |
| |
Authors: | HUO Xian-jun |
| |
Affiliation: | HUO Xian-jun (Power ( Beijing) Product Certification Center Co.,Ltd ,Beijing 100011, China) |
| |
Abstract: | In 6 kV power supply system,aiming at operating over-voltage produced by inductance load and grounding over-voltage produced by single phase grounding,to adopt additional installation of first,second harmonic removing devices on voltage transformer,additional installation of intelligent type grounding compensation and measures of additional installation of over-voltage protecter on motor and transformer side is a better way and an effective method to eliminate over-voltage threats to power supply system. |
| |
Keywords: | 6 kV power supply system over-voltage harmonic removing device grounding compensation |
本文献已被 CNKI 维普 万方数据 等数据库收录! |