首页 | 本学科首页   官方微博 | 高级检索  
     


Transient electromagnetic interference in substations
Authors:Wiggins  CM Thomas  DE Nickel  FS Salas  TM Wright  SE
Affiliation:BDM Int. Inc., Albuquerque, NM;
Abstract:Electromagnetic interference levels on sensitive electronic equipment are quantified experimentally and theoretically in air and gas insulated substations of different voltages. Measurement techniques for recording interference voltages and currents and electric and magnetic fields are reviewed and actual interference data are summarized. Conducted and radiated interference coupling mechanisms and levels in substation control wiring are described using both measurement results and electromagnetic models validated against measurements. The nominal maximum field and control wire interference levels expected in the switchyard and inside the control house from switching operations, faults, and an average lightning strike are estimated using high frequency transient coupling models. Comparisons with standards are made and recommendations given concerning equipment shielding and surge protection