首页 | 本学科首页   官方微博 | 高级检索  
     


Diagnosis Criterion of Abnormality of Transformer Winding by Frequency Response Analysis (FRA)
Authors:SATORU MIYAZAKI  YOSHINOBU MIZUTANI  AKIRA TAGUCHI  JUNICHI MURAKAMI  NAOKAZU TSUJI  MASAHIRO TAKASHIMA  OSAMU KATO
Affiliation:1. Central Research Institute of Electric Power Industry, Japan;2. Kyushu Electric Power Co., Inc., Japan;3. Tohoku Electric Power Co., Inc., Japan;4. Chugoku Electric Power Co., Inc., Japan
Abstract:Frequency response analysis (FRA) is a powerful technique to detect internal abnormalities within power transformers. However, diagnosis criteria of power transformers by FRA have not been fully established yet. In this paper, a new evaluation method of degree of identification between two transfer functions is proposed. In the proposed method, a frequency window is employed and cross‐correlation factor is calculated with moving the window. Furthermore, the proposed method is applied to transfer functions of real transformers with or without some abnormalities. Based on this discussion, objective criteria for diagnosis of abnormalities of transformer windings by FRA are proposed. The proposed criteria are based on a few data of transformers with some abnormalities. Therefore, the proposed criteria are tentative and they would be improved by accumulation of further data.
Keywords:power transformer  diagnosis of abnormality of winding  criterion  frequency response analysis
设为首页 | 免责声明 | 关于勤云 | 加入收藏