首页 | 本学科首页   官方微博 | 高级检索  
     

600MW机组空气预热器堵灰原因分析及处理措施
引用本文:郑鹏.600MW机组空气预热器堵灰原因分析及处理措施[J].重庆电力高等专科学校学报,2009,14(4):1-4,17.
作者姓名:郑鹏
作者单位:华能珞璜电厂,重庆,402283
摘    要:结合珞璜电厂三期5#炉空气预热器堵灰事件,从理论和实际两个方面详细分析空气预热器堵灰的原因,从而提出提高受热面壁温等预防堵灰的措施,以确保空气预热器的正常运行。

关 键 词:空气预热器  低温腐蚀  露点温度  堵灰

Causes and Measures of Air Preheater Fouling in 600MW Unit of Huaneng Luohuang Power Plant
ZHENG Peng.Causes and Measures of Air Preheater Fouling in 600MW Unit of Huaneng Luohuang Power Plant[J].Journal of Chongqing Electric Power College,2009,14(4):1-4,17.
Authors:ZHENG Peng
Affiliation:ZHENG Peng (Huaneng Luohuang Power Plant,Chongqing 402283,China)
Abstract:Considering No.5 boiler air preheater fouling event in Luohuang Power Plant,the paper gets the conclusion of the air preheater fouling cause through a detailed analysis from the theoretical and practical aspects,that is,the wall temperature of the heating surface is below the gas dew point,which is caused by SO3 in the flue gas condensed into sulfuric acid on the heated surface leading to low-temperature corrosion of metal.Therefore,the paper proposes to increase the wall temperature of the heat surfacing f...
Keywords:air preheater  low-temperature corrosion  dew-point temperature  fouling  
本文献已被 CNKI 维普 万方数据 等数据库收录!
设为首页 | 免责声明 | 关于勤云 | 加入收藏

Copyright©北京勤云科技发展有限公司  京ICP备09084417号