首页 | 本学科首页   官方微博 | 高级检索  
     


Simplified calculation method for design cooling loads in underfloor air distribution (UFAD) systems
Authors:Stefano Schiavon  Kwang Ho Lee  Fred Bauman  Tom Webster
Affiliation:Center for the Built Environment, University of California, 390 Wurster Hall, Berkeley, CA 94720-1839, USA
Abstract:This paper describes the development of a simplified calculation method for design cooling loads in underfloor air distribution (UFAD) systems. The simplified design tool is able to account for key differences between UFAD and traditional mixing overhead (OH) systems. These include: (1) difference between design day cooling load profiles, (2) impact of a thermally stratified environment for UFAD versus well-mixed for OH, and (3) impact of heat transfer (temperature gain) in underfloor air supply plenums. The new design tool allows the use of a familiar load calculation procedure for OH mixing systems as input to the UFAD design tool. Based on 87 EnergyPlus simulations, four regression models have been developed to transform the OH cooling load into the UFAD cooling load, and then to split this total load between the supply plenum, zone (room), and return plenum. The regression models mainly depend on floor level, and position (interior or perimeter) and orientation of the zone under analysis. Although considered in the analysis, supply air temperature, window-to-wall ratio, internal heat gain, plenum configuration, climate, presence of the carpet and structure type do not strongly influence the developed models. The results show that, generally, UFAD has a peak cooling load 19% higher than an overhead cooling load and 22% and 37% of the total zone UFAD cooling load goes to the supply plenum in the perimeter and interior, respectively.
Keywords:
本文献已被 ScienceDirect 等数据库收录!
设为首页 | 免责声明 | 关于勤云 | 加入收藏

Copyright©北京勤云科技发展有限公司  京ICP备09084417号