Influence of Clearance Volume on Performance of Reciprocating Compressor
Wei Huijun,Feng Hai,Zhao Xumin,Xu Min,Chen Juanjuan.Influence of Clearance Volume on Performance of Reciprocating Compressor[J].Journal of Refrigeration,2021,42(1):134-139.
Authors:Wei Huijun  Feng Hai  Zhao Xumin  Xu Min  Chen Juanjuan
Affiliation:(National Engineering Research Center of Green Refrigeration Equipment, Zhuhai, 519070, China;Guangdong Key Laboratory of Refrigeration Equipment and Energy Conservation Technology, Zhuhai, 519070, China;Green Electric Appliances, Inc. of Zhuhai, Zhuhai, 519070, China)
Abstract:The cooling capacity of a reciprocating compressor can be finely adjusted using the clearance volume.To study the influence of the clearance volume and the intermediate clearance volume on the performance of the reciprocating compressor,the clearance volume was taken as a single variable to investigate the relationship between parameters such as the cooling capacity and COP and clearance volume under the designated conditions(evaporation temperature of 23.3℃and condensation temperature of 54.4℃).The result shows that when the clearance volume or the intermediate clearance volume increases,the COP first increases and then decreases,and increasing the intermediate clearance volume is better than the clearance volume for increasing the COP.Among them,when the relative clearance is 0.56%-0.73%,the performance of the reciprocating compressor reaches the maximum value,and the COP can be increased by 0.62%.When the relative intermediate clearance is 18%,the cooling capacity can be reduced by 10%,and the COP increases by 1.31%.In addition,increasing the intermediate clearance volume also helps reduce the exhaust temperature of the compressor.
Keywords:reciprocating compressor  clearance volume  coefficient of performance  standard conditions