新型空气-水双热源复合热泵系统除霜特性及能耗
引用本文:徐俊芳,赵耀华,全贞花,王会粉,赵会刚,王皆腾. 新型空气-水双热源复合热泵系统除霜特性及能耗[J]. 化工学报, 2018, 69(6): 2646-2654. DOI: 10.11949/j.issn.0438-1157.20171277
作者姓名:徐俊芳  赵耀华  全贞花  王会粉  赵会刚  王皆腾
作者单位:1. 北京工业大学建筑工程学院, 北京 100022;2. 北京市住房和城乡建设科学技术研究所, 北京 100021
基金项目:国家科技支撑计划项目(2012BAA13B02)。
摘    要:基于新型空气-水双热源复合热泵系统(AWDSHPS-N),实验研究了AWDSHPS-N采用冷凝器出口制冷剂再冷却除霜(D-I)、低温热水除霜(D-Ⅱ)、低温热水+冷凝器出口制冷剂再冷却除霜(D-Ⅲ)3种除霜模式进行除霜时对系统整体性能系数(COP)的影响,除霜期间系统运行特性及除霜所消耗的能量,并与逆循环除霜模式进行了对比分析。测试工况下的实验结果表明,除霜模式D-I和D-Ⅲ仅使系统整体COP较结霜运行期间的COP分别降低了0.42%和3.93%;D-Ⅱ除霜期间系统的制热功率和COP分别较结霜运行期间提高了27.4%和17.8%。D-I、D-Ⅱ和D-Ⅲ完成一次除霜能耗仅分别为逆循环除霜能耗的3.11%、34.78%和28.26%;采用此3种除霜模式时系统整体COP较采用逆循环除霜时分别提高了26.06%、29.79%和17.02%。

关 键 词:复合热泵  再生能源  除霜  性能系数  优化  压缩机  
收稿时间:2017-09-19
修稿时间:2017-11-06

Defrosting characteristics and energy consumption of new air-water dual source composite heat pump system
XU Junfang,ZHAO Yaohua,QUAN Zhenhua,WANG Huifen,ZHAO Huigang,WANG Jieteng. Defrosting characteristics and energy consumption of new air-water dual source composite heat pump system[J]. Journal of Chemical Industry and Engineering(China), 2018, 69(6): 2646-2654. DOI: 10.11949/j.issn.0438-1157.20171277
Authors:XU Junfang  ZHAO Yaohua  QUAN Zhenhua  WANG Huifen  ZHAO Huigang  WANG Jieteng
Affiliation:1. College of Architecture and Civil Engineering, Beijing University of Technology, Beijing 100022, China;2. Beijing Science and Technology Institute of Housing and Urban-Rural Development, Beijing 100021, China
Abstract:Based on the operation testing of new air-water double source composite heat pump system (AWDSHPS-N), three defrosting modes were investigated under the same ambient condition, which included the condenser outlet refrigerant recooling defrosting(D-I), the low temperature-hot water defrosting(D-Ⅱ), the condenser outlet refrigerant recooling and low temperature-hot water defrosting at same time (D-Ⅲ). Total coefficient of performance (COP) of AWDSHPS-N was used to evaluate the influence of the three modes. The influence on the total COP, defrosting operating characteristics and energy consumption of D-I, D-Ⅱ and D-Ⅲ were discussed and compared with those in the reverse-cycle defrosting mode, under the same ambient condition. The results of test conditions indicated that for D-I and D-Ⅱ, the total COP can be decreased by 0.42% and 3.93%, respectively, compared with the COP of frosting period. The heating power and COP during D-Ⅱ defrosting were 27.4% and 17.8% higher than those of frosting operation, respectively. The total COP of AWDSHPS-N choosing D-I, D-Ⅱ and D-Ⅲ were 26.06%, 29.79% and 17.02% higher than that of verse-cycle defrosting, and the defrosting energy consumption of D-I, D-Ⅱ and D-Ⅲ were only 3.11%, 34.78% and 28.26% of the reverse-cycle defrosting energy consumption.
Keywords:composite heat pump  renewable energy  defrosting  coefficient of performance  optimization  compressor  