首页 | 本学科首页   官方微博 | 高级检索  
     

基于X射线激励下的局部放电定位
引用本文:黄兴泉,郭琳.基于X射线激励下的局部放电定位[J].华北电力大学学报,1999,26(4):1-5.
作者姓名:黄兴泉  郭琳
作者单位:[1]华北电力大学 [2]郑州电力高等专科学校
摘    要:X射线照射绝缘介质,可以激发或加强介质中的气隙放电;调节X射线照射的方位并检测因射线激励所产生的局部放电信号,可有效地确定局部放电的部位。本文通过研究X射线激励对变压器模型中气隙放电的影响,探讨X射线激励下的局部放电定位,为X射线激励下局部放电测量和定位技术在油纸绝缘系统中的应用奠定基础。

关 键 词:x射线  局部放电  定位

Location of partial Discharge by X-ray Irradiation
HUANG Xing-quan, GUO Lin, LI Cheng-rong,LIU Shu-chun.Location of partial Discharge by X-ray Irradiation[J].Journal of North China Electric Power University,1999,26(4):1-5.
Authors:HUANG Xing-quan  GUO Lin  LI Cheng-rong  LIU Shu-chun
Abstract:There are some defects existing in the power transformers such as manufacture craft and insulationdeterioration. To this end, partial discharge tests are often performed as a final check on quality. With conventional PD measurement technique, PD detection sensitivity is often limited by the availability of electrons necessary to initiate PD in defects. Statistical time lag, i. e., the time required for a discharge initiating free electronto appear in the defect, could make a dangerous defect undetectable. The application of X-rays during electricalPD measurements can increase the free electron production rate in the cavity and decrease the statistical time lag,resulting in an improved PD sensitivity. Partial discharge is induced or intensified when dielectric is irradiatedby X-ray, the location of partial discharge can been fixed on by modulating orientation of X-ray irradiation anddetecting partial discharge signal because of X-ray irradiation.
Keywords:X-ray  partial discharge  location  
本文献已被 CNKI 维普 等数据库收录!
设为首页 | 免责声明 | 关于勤云 | 加入收藏

Copyright©北京勤云科技发展有限公司  京ICP备09084417号