首页 | 本学科首页   官方微博 | 高级检索  
     

SF_6电气设备塑袋包扎检漏方法误差分析及检漏仪的现场校验
引用本文:辛夫,吴雪峰.SF_6电气设备塑袋包扎检漏方法误差分析及检漏仪的现场校验[J].高压电器,2011,47(6).
作者姓名:辛夫  吴雪峰
作者单位:西安西电开关电气有限公司,西安,710077
摘    要:工厂内及安装现场检查SF_6组合电气设备气体密封性能一般采用塑袋局部封装包扎检漏方法,影响该检漏方法结果的因素较多,环境温度、气压、包扎塑袋体积测估以及检测仪器的误差等均会影响检测结果,按文中讨论的方法加以注意和控制,可将检漏检验误差控制在±50%以内。

关 键 词:漏气率  年漏气率  误差  现场比对校验

Error Analysis of Leak Detection Method for SF6 Electrical Equipmen's Packaging with Plastic Bags and the Detector's On-site Calibration
XIN Fu,WU Xue-feng.Error Analysis of Leak Detection Method for SF6 Electrical Equipmen's Packaging with Plastic Bags and the Detector's On-site Calibration[J].High Voltage Apparatus,2011,47(6).
Authors:XIN Fu  WU Xue-feng
Abstract:For inspection of SF_6 leakage at factory and installation spot,the general method is local packaging with plastic bags for GIS.There're many factors that can affect the result of this method,for example, environmental temperature,atmosphere pressure,volume of plastic bags estimating and the detector's error etc. But if the inspector paid attention to the problems and controlled according to the method of this essay,then the error of the leakage inspection can be controlled within±50%or less.
Keywords:leak rate  annual leak rate  error  on-site comparison calibration