220kV架空线路故障断线原因试验检测分析
引用本文:彭向阳.220kV架空线路故障断线原因试验检测分析[J].高压电器,2011,47(6):48-52,57.
作者姓名:彭向阳
作者单位:广东电力科学研究院,广东,510600
摘    要:介绍了220 kV线路断线故障经过和临时处理措施,通过对断线样品进行拉力、通流、电镜和能谱分析等机械、电气性能对比试验和检测,分析导线断线原因.指出故障前断口处导线已存在显著的通流缺陷,同时由于线路运行年限较长机械强度下降,因局部发热恶性循环发展和强度逐步丧失最终导致小负荷电流下导线断线.强调要控制线路负荷和加强红外测...

关 键 词:输电线路  断线故障  试验检测  原因分析

Causation Analysis by Test and Detection on Break Fault of 220 kV Overhead Transmission Line
PENG Xiang-yang.Causation Analysis by Test and Detection on Break Fault of 220 kV Overhead Transmission Line[J].High Voltage Apparatus,2011,47(6):48-52,57.
Authors:PENG Xiang-yang
Abstract:The paper introduces line break failure and temporary treatment measures of 220 kV overhead transmission line,then gives the reasons for disconnection of wires through performance mechanical and electrical comparison tests of the broken samples such as pull test,current carrier and temperature rising test,electron microscopy test and energy spectrum analysis.Points out that as a long line running years,the wire had existed significant defects of machinery and electricity before the fracture,and then led to wire break under a small load current due to vicious cycle of local heat development and gradual loss of strength.At the end this paper,stresses the need to control load current and infrared temperature measurement to remove security risks of line,and suggests taking out technical transformation project of fault line as soon as possible.
Keywords:overhead transmission line  wire breaking fault  test and detection  causation analysis