Real time evaluation of DWT-based high impedance fault detection in EHV transmission
Authors:Doaa khalil Ibrahim  El Sayed Tag Eldin  Essam M. Aboul-Zahab  Saber Mohamed Saleh
Affiliation:1. Department of Electrical and Machine Engineering, Cairo University, Giza, Egypt;2. Ministry of Electricity and Energy, Thermal Power Plant, Giza, Egypt
Abstract:It is possible to capture the required travelling wave information contained in fault transients using wavelet transform. This paper presents practical real time testing for the high impedance fault (HIF) detection algorithm based on real time accidents data. The proposed scheme is implemented for HIF detection in extra high voltage transmission lines. The classifier is based on an algorithm that uses recursive method to sum the absolute values of the high frequency signal generated over one cycle and shifting one sample. Characteristics of this scheme are analyzed by extensive real time studies that clearly reveal that this technique can accurately detect HIFs in the EHV transmission lines within only half a cycle from the instant of fault occurrence. The reliability of this scheme is not affected by different fault conditions such as fault distance and fault inception angle.
Keywords:High impedance fault (HIF)   Wavelet transform   Real time testing