Experimental study on a new internally cooled/heated dehumidifier/regenerator of liquid desiccant systems
Authors:Yonggao Yin   Xiaosong Zhang   Geng Wang  Lei Luo
Affiliation:aSchool of Energy and Environment, Southeast University, 2# SiPaiLou Road, Nanjing, Jiangsu 210096, China
Abstract:For providing good performance of dehumidifier and regenerator with certain dimensions, a new type of internally cooled/heated dehumidifier/regenerator based on the plate–fin heat exchanger (PFHE) was designed. To investigate the behavior of the new equipment, an experimental setup was established in an environment chamber with regulable temperature and humidity air. By the internally cooled dehumidification testing, effects of the cooling water temperature, the air flow rate and the desiccant temperature on the dehumidification performance and the cooling efficiency were presented. The behavior of internally cooled dehumidification process was compared with that of the adiabatic dehumidification process. The results suggested that the cooling efficiency decreased with the increasing of the cooling water temperature and desiccant with low temperature could bring more mass transfer coefficients. There is an optimal air flow rate to achieve the maximum absolute humidity decrease of the air. By the internally heated regeneration testing, effects of the air flow rate and the desiccant inlet temperature on the regeneration performance and air outlet parameters were discussed and also compared with those of the adiabatic regeneration process. It was concluded that the regeneration efficiency of internally heated regeneration was more than that of the adiabatic regeneration, and the internally heated regenerator could offer better thermal performance.
Keywords:Air conditioning   Dehumidifier   Desiccant   Design   Heat exchanger   Regenerator   Finned tube   ExperimentMots clé  s: Conditionnement d'air    shumidificateur    shydratant   Conception   É  changeur de chaleur        rateur   Tube aileté     Expé  rimentation
本文献已被 ScienceDirect 等数据库收录!
设为首页 | 免责声明 | 关于勤云 | 加入收藏

Copyright©北京勤云科技发展有限公司  京ICP备09084417号