首页 | 本学科首页   官方微博 | 高级检索  
     


Two-stage heat pump system with vapor-injected scroll compressor using R410A as a refrigerant
Authors:Xudong Wang  Yunho Hwang  Reinhard Radermacher
Affiliation:aAir-Conditioning, Heating, and Refrigeration Institute, 2111 Wilson Boulevard, Suite 500, Arlington, VA 22201-3001, USA;bCenter for Environmental Energy Engineering, Department of Mechanical Engineering, University of Maryland, College Park, MD 20742, USA
Abstract:Refrigerant vapor-injection technique has been well justified to improve the performance of systems in refrigeration applications. However, it has not received much attention for air conditioning applications, particularly for air conditioning in hot climates and for heat pumping in cold climates. In this study, the performance of an 11 kW R410A heat pump system with a two-stage vapor-injected scroll compressor was experimentally investigated. The vapor-injected scroll compressor was tested with the cycle options of both flash tank and internal heat exchanger configurations. A cooling capacity gain of around 14% with 4% COP improvement at the ambient temperature of 46.1 °C and about 30% heating capacity improvement with 20% COP gain at the ambient temperature of −17.8 °C were found for the vapor-injected R410A heat pump system as compared to the conventional system which has the same compressor displacement volume.
Keywords:Heat pump  Air–  air  Scroll compressor  Injection  R410A  Experiment  Performance  COPMots clé  s: Pompe à  chaleur  Air–  air  Compresseur à  spirale  Injection  R410A  Expé  rimentation  Performance  COP
本文献已被 ScienceDirect 等数据库收录!
设为首页 | 免责声明 | 关于勤云 | 加入收藏

Copyright©北京勤云科技发展有限公司  京ICP备09084417号