首页 | 本学科首页   官方微博 | 高级检索  
     

闭式水系统中补水泵的设置
引用本文:卫军峰,左贤龄.闭式水系统中补水泵的设置[J].暖通空调,2007,37(8):128-129,160.
作者姓名:卫军峰  左贤龄
作者单位:1. 中国建筑标准设计研究院
2. 中国航天建筑设计研究院
摘    要:结合相关规范的规定,提出了暖通空调闭式水系统正常补水泵和事故补水泵应分开设置。正常补水泵用于水系统正常运行时的补水,流量宜为系统水容量的1%或者供热系统循环流量的2%,并进行变频调速控制;事故补水泵台数不宜过多也不宜少于2台;事故补水泵和正常补水泵均可不设备用泵。

关 键 词:补水泵  变频  节能  闭式水系统
修稿时间:2005-06-202005-11-18

Setup of make-up water pumps for closed water systems
Wei Junfeng,Zuo Xianling.Setup of make-up water pumps for closed water systems[J].Journal Heating Ventilating and Airconditioning,2007,37(8):128-129,160.
Authors:Wei Junfeng  Zuo Xianling
Abstract:With the provisions in relating codes,states that normal make-up water pumps and accident make-up water pumps should be set separately for a closed HVAC water system.Normal make-up water pumps provide make-up water in normal operation with the water flow rate of one percent of system water volume or of two percent of circulating water quantity of a heating system,applying variable frequency control at the same time.There should not be too many accident make-up water pumps in a system,but the number of the pump should not be less than two.It is unnecessary to install spare pumps for normal and accident make-up water pumps.
Keywords:make-up water pump  variable frequency  energy saving  closed water system