500kV开关防跳功能异常的分析及解决方案
引用本文:李明.500kV开关防跳功能异常的分析及解决方案[J].广东输电与变电技术,2009,11(6):30-33.
作者姓名:李明
作者单位:广东电网公司中山供电局
摘    要:通过对500kV香山变电站500kV开关防跳回路出现故障现象进行分析,阐述了开关本体防跳回路与操作箱控制回路配合的动作原理,揭示了开关本体防跳回路与操作箱控制回路之间存在的寄生回路问题,并提出解决技术方案。

关 键 词:防跳继电器  开关本体防跳  操作箱跳寄生回路

Analysis and Solution of the Abnormality of 500kV Circuit Breaker Anti-pumping Function
Li Ming.Analysis and Solution of the Abnormality of 500kV Circuit Breaker Anti-pumping Function[J].Guangdong Power Transmission Technology,2009,11(6):30-33.
Authors:Li Ming
Affiliation:Li Ming(Guangdong Power Grid Corporation Zhongshan Power Supply Bureau)
Abstract:Through analyzing the abnormality of the 500kV circuit breakers anti-pumping circuit in 500kV Xiangshan substation, the coordination between the anti-pumping circuit in circuit breaker itself and the operating circuit inside control kiosk is described. A parasitic circuit in between circuit breaker and the kiosk is found and then solution method to this problem is worked out.
Keywords:Anti-pumping relay Anti-pumping in C/B itself Parasitic circuit of control kiosk