Study on Inter-turn Short Circuit Fault Detection of Dry-type Air-core Reactor Based on Power Factor Method
YIN Ruihan,DING Guocheng,YANG Haitao,CHEN Qingtao,YU Hua,LIU Quanfeng,ZHENG Lijun,WANG Yuanpeng. Study on Inter-turn Short Circuit Fault Detection of Dry-type Air-core Reactor Based on Power Factor Method[J]. Power Capacitor $ Reactive Power Compensation, 2020, 0(2): 80-85
Authors:YIN Ruihan  DING Guocheng  YANG Haitao  CHEN Qingtao  YU Hua  LIU Quanfeng  ZHENG Lijun  WANG Yuanpeng
Affiliation:(State Grid Anhui Electric Power Research Institute,Hefei 230003,China;State Grid Shanxi Electric Power Co.,Ltd.,Taiyuan 030001,China;Xi’an Herong Electric Power Equipment Co.,Ltd.,Xi’an 710200,China;Xi’an Jiaotong University,Xi’an 710049,China)
Abstract:Dry-type air core reactor is used widely in power systems and its inter-turn short circuit is the common fault.For reducing the loss due to the short circuit fault and increasing on line detection accuracy of inter-turn short circuit fault of reactor,in this paper,the inter-turn short circuit on line detection method based on the power factor is proposed.The theoretical analysis of the reactor in normal operation and power factor variation of the reactor in the inter-turn short circuit is made on the basis of electromagnetic field theory,the ANSYS Maxwell is used to establish a finite element model to simulate the calculation of power factor variation.Then,the reactor sample with 13 encapsulation and total of 41 layers of coils is tested at different voltages and the feasibility of the detection method is verified by the combination of simulation and test result.
Keywords:dry-typeair-corereactor  power factor method  inter-turn short circuit  detection