双回线路跨线故障及保护动作行为分析
引用本文:孟恒信,朱良肄,张涛. 双回线路跨线故障及保护动作行为分析[J]. 电力系统自动化, 2006, 30(18): 103-107
作者姓名:孟恒信  朱良肄  张涛
作者单位:山西省电力科学研究院,山西省,太原市,030001;太原供电公司,山西省,太原市,030009;山西省电力公司电力调度通信中心,山西省,太原市,030001
摘    要:以山西220kV系统某线路的一次实际跨线故障录波数据为基础,分析了同杆双回线路保护安装处的电流电压特征,研究了该线路上4套不同厂家、不同型号常规微机型线路保护的动作行为,提出了同杆并架双回线保护选型应注意的问题。结果表明,异名相跨线故障期间,各端保护可以检测到零序电流,但无零序电压;变化量方向元件可以正确判断方向;采用零序电流(?)_0和负序电流(?)_(2A)构成的稳态量选相元件能正确选相;零序方向元件的动作行为不确定;相间测量阻抗增大、接地测量阻抗减小均不能正确反映故障位置。

关 键 词:同杆并架双回线  跨线故障  微机保护  故障录波数据
收稿时间:2005-12-21
修稿时间:2005-12-212006-04-14

Analysis of Overhead Line Fault and Protection of Double-circuit Transmission Lines
MENG Hengxin,ZHU Liangyi,ZHANG Tao. Analysis of Overhead Line Fault and Protection of Double-circuit Transmission Lines[J]. Automation of Electric Power Systems, 2006, 30(18): 103-107
Authors:MENG Hengxin  ZHU Liangyi  ZHANG Tao
Abstract:Based on the actual overhead line fault recorded data of a transmission line in the 220 kV electric power system of Shanxi Province, the current and voltage characteristics at the site of the protection equipment for double-circuit transmission lines on the same pole are analyzed. The action-behaviors of four conventional microcomputer-based line protections with different types and from different manufactures are studied. The problems related to the protection selection of double-circuit transmission lines are highlighted. The results show that: (1)the zero-sequence current but not the voltage can be detected by the protections located at both sides of transmission lines during overhead line fault between different phases; (2)the differential directional elements can be identified accurately; (3)the steady-state phase selection elements formed by the zero- sequence current I_0 and negative-sequence current I_(2A) can be used to select phase exactly; (4)the action-behaviors of the zero- sequence directional element is uncertain; (5)both the increase of the measured impedance between phases and the decrease of the measured grounding impedance can not reflect the fault location correctly.
Keywords:double-circuit transmission line on the same pole   overhead line fault   microcomputer-based protection   fault recording data
本文献已被 CNKI 万方数据 等数据库收录!
点击此处可从《电力系统自动化》浏览原始摘要信息