特殊工况下换流变零序差动保护误动机理分析及对策研究
引用本文:翁汉,李昊威,万毅,李振兴,黄景光,林湘宁.特殊工况下换流变零序差动保护误动机理分析及对策研究[J].电力系统保护与控制,2020,48(5):56-64.
作者姓名:翁汉  李昊威  万毅  李振兴  黄景光  林湘宁
作者单位:三峡大学梯级水电站运行与控制湖北省重点实验室,湖北宜昌 443002;三峡电能有限公司,湖北宜昌 443002;强电磁工程与新技术国家重点实验室(华中科技大学),湖北武汉 430074
基金项目:国家自然科学基金项目资助(51607106); 湖北省梯级水电站运行与控制重点实验室(三峡大学)开放基金项目资助(2018KJX05)
摘    要:针对高压直流输电工程中换流变压器零序差动保护误动的案例,分析了特高压换流变中性线上电流互感器在长时间单极-大地运行伴随交流系统高阻故障工况下饱和机理。采用基于工程实际参数的特高压直流输电模型进行仿真分析,揭示换流变零序差动保护误动原因。并根据区内、外故障时保护两侧自产零序电流和中性线零序电流极性差异,提出一种基于S变换相位差的换流变零序差动保护闭锁新判据,以解决特殊工况下换流变零序差动保护误动的问题。通过仿真验证该判据的有效性。

关 键 词:换流变压器  零序差动保护  电流互感器饱和  S变换  相位差
收稿时间:2019/4/16 0:00:00
修稿时间:2019/7/23 0:00:00

Mechanism and countermeasures of mal-operation of converter transformer zero-sequence differential protection under special conditions
WENG Hanli,LI Haowei,WAN Yi,LI Zhenxing,HUANG Jingguang and LIN Xiangning.Mechanism and countermeasures of mal-operation of converter transformer zero-sequence differential protection under special conditions[J].Power System Protection and Control,2020,48(5):56-64.
Authors:WENG Hanli  LI Haowei  WAN Yi  LI Zhenxing  HUANG Jingguang and LIN Xiangning
Affiliation:Hubei Provincial Key Laboratory for Operation and Control of Cascaded Hydropower Station, China Three Gorges University, Yichang 443002, China,Hubei Provincial Key Laboratory for Operation and Control of Cascaded Hydropower Station, China Three Gorges University, Yichang 443002, China,Three Gorges Electric Energy Co., Ltd., Yichang 443002, China,Hubei Provincial Key Laboratory for Operation and Control of Cascaded Hydropower Station, China Three Gorges University, Yichang 443002, China,Hubei Provincial Key Laboratory for Operation and Control of Cascaded Hydropower Station, China Three Gorges University, Yichang 443002, China and China State Key Laboratory of Electromagnetic Engineering Huazhong University of Science and Technology, Wuhan 430074, China
Abstract:Aiming at the cases of mal-operations of zero-sequence differential protection of converter transformers in the HVDC transmission project, the saturation mechanism of current transformers on the neutral line of the UHVDC converter transformer under long-term unipolar-earth operation accompanied with high-impedance fault conditions of AC system is analyzed. The reason of the mal-operations of the zero-sequence differential protection is revealed based on the UHVDC model, which adopts the actual engineering parameters. According to the polarity difference between the self-produced zero-sequence current and the zero-sequence current on the neutral line on both sides of the protection under internal and external faults, a novel blocking criterion of zero-sequence differential protection for converter transformers based on S-transform phase angle difference is proposed to solve the mal-operation of the zero-sequence differential protection under special conditions. The validity of the criterion is verified by simulation tests. This work is supported by National Natural Science Foundation of China (No. 51607106) and Open Foundation of Hubei Provincial Key Laboratory for Operation and Control of Cascaded Hydropower Station (China Three Gorges University) (No. 2018KJX05).
Keywords:converter transformer  zero-sequence differential protection  saturation of current transformer  S-transform  phase angle difference