Exposure to fine particulate matter in ten night clubs in Athens Greece: Studying the effect of ventilation, cigarette smoking and resuspension |
| |
Authors: | Christos Halios Mat Santamouris Maria Kapsalaki Dimitris Tsakos |
| |
Affiliation: | a Department of Environmental Physics and Meteorology, Faculty of Physics, University of Athens, Building Phys 5, University Campus, Athens, 15784 Greece b Faculty of Engineering, University of Porto, MIT-Portugal |
| |
Abstract: | The aim of the present work is to study the occupants' exposure to fine particulate concentrations in ten nightclubs (NCs) in Athens, Greece. Measurements of PM1 and PM2.5 were made in the outdoor and indoor environment of each NC. The average indoor PM1 and PM2.5 concentrations were found to be 181.77 μg m− 3 and 454.08 μg m− 3 respectively, while the corresponding outdoor values were 11.04 μg m− 3 and 32.19 μg m− 3. Ventilation and resuspension rates were estimated through consecutive numerical experiments with an indoor air quality model and were found to be remarkably lower than the minimum values recommended by national standards. The relative effects of the ventilation and smoking on the occupants' exposures were examined using multiple regression techniques. It was found that given the low ventilation rates, the effect of smoking as well as the occupancy is of the highest importance. Numerical evaluations showed that if the ventilation rates were at the minimum values set by national standards, then the indoor exposures would be reduced at the 70% of the present exposure values. |
| |
Keywords: | Indoor exposure Resuspension Ventilation Nightclubs PM1 PM2.5 |