一起220kV GIS设备故障跳闸原因分析
引用本文:张继龙,杨博超,郭赫. 一起220kV GIS设备故障跳闸原因分析[J]. 河北电力技术, 2010, 29(4): 49-51
作者姓名:张继龙  杨博超  郭赫
作者单位:石家庄供电公司,石家庄,050051
摘    要:介绍一起220 kV GIS设备发生W相线路侧接地故障造成三相开关跳闸的情况,通过故障检查认为,跳闸是由设备内部绝缘件表面附着油迹,造成设备在运行中发生内部闪络放电引起的,通过深入分析设备内部绝缘件表面出现油迹和发生绝缘击穿的原因,提出加强设备安装与运行维护中对抽真空设备管理的建议。

关 键 词:GIS  接地故障  油迹  闪络放电  盆式绝缘子  真空泵

Cause Analysis on One Fault Trip of 220 kV GIS Equipment
Zhang Jilong,Yang Bochao,Guo He. Cause Analysis on One Fault Trip of 220 kV GIS Equipment[J]. Hebei Electric Power, 2010, 29(4): 49-51
Authors:Zhang Jilong  Yang Bochao  Guo He
Affiliation:Zhang Jilong,Yang Bochao,Guo He
Abstract:This paper introduces the situation of three-phase switch trip caused by earthing fault of W-phase line-side of a 220 kV GIS equipment.By the fault test result,that trip was due to the oil attached to the surface of the internal insulated part,leading to internal flashover discharge during the operation,analyzes in-depth the cause of the oil attached to the surface of the equipment internal insulated part and insulation breakdown occurred,and proposes the improvement for strengthening the equipment installation and the management of the vacuum equipment during the operation maintenance.
Keywords:GIS