首页 | 本学科首页   官方微博 | 高级检索  
     


Air-side performance of brazed aluminum heat exchangers under dehumidifying conditions
Authors:Man-Hoe Kim  Clark W Bullard
Abstract:An experimental study for air-side thermal-hydraulic performance of brazed aluminum heat exchangers under dehumidifying conditions has been performed. For 30 samples of louvered fin heat exchangers with different geometrical parameters, the heat transfer and pressure drop characteristics for wet surface were evaluated. The test was conducted for air-side Reynolds number in the range of 80–300 and tube-side water flow rate of 320 kg/h. The dry- and wet-bulb temperatures of the inlet air for heat exchangers were 27 and 19 °C, respectively and the inlet water temperature was 6 °C. The air-side thermal performance data for cooling and dehumidifying conditions were analyzed using effectiveness-NTU method for cross-flow heat exchanger with both fluids unmixed. The test results are reported, compared with those for the dry surface heat exchangers, in terms of sensible j factor and friction factor f, as functions of Reynolds number based on louver pitch. The correlations for j and f factors are developed within rms errors of ±16.9 and ±13.6%, respectively.
Keywords:Air cooler  Heat exchanger  Water/air  Material  Aluminium  Enhanced surface  Geometry  Dehumidification  Heat transfer  ModellingAuthor Keywords: Refroidisseur d'air  É  changeur de chaleur  Eau/air  Maté  riau  Aluminium  Surface augmenté  e    omé  trie    shumidification  Transfert de chaleur  Modé  lisation
本文献已被 ScienceDirect 等数据库收录!