10 kV配电网中性点两种接地方式的选择
引用本文:刘顺桂.10 kV配电网中性点两种接地方式的选择[J].广东电力,1999,12(6):14-15.
作者姓名:刘顺桂
作者单位:深圳供电局,广东,深圳,518001
摘    要:分析了10kV配电网中性点经小电阻接地及经自动跟踪补偿消弧线圈接地配小电流微机选线装置切除单相接地故障的可靠性和供电可靠性。通过分析比较,认为:对于全电缆配电网,宜选择中性点经小电阻接地方式;对于混合网,如果架空线所占比例较大,宜采用自动跟踪补偿消弧线圈接地配微机选线装置。

关 键 词:配电网  中性点接地方式  小电阻接地  消弧线圈接地

Selection between two neutral grounding modes for 10 kV distrib ution network
LIU Shun-gui.Selection between two neutral grounding modes for 10 kV distrib ution network[J].Guangdong Electric Power,1999,12(6):14-15.
Authors:LIU Shun-gui
Abstract:In 10 kV distribution network,neutral is grounded mainly by small resistance or automatic tracking and compensating arc suppression coil with trickle micro processor based line selector.The reliability of power supply and single phase ground fault elimination of these two practices are analyzed and compared.It is concluded that the former practice is suitable for distribution network solely formed with cables,while the latter suitable for mixed network of which overhead lines account for a larger proportion.
Keywords:distribution network  neutral grounding modes  grounding by small resistance  grounding by arc  suppression coil  