首页 | 本学科首页   官方微博 | 高级检索  
     


ROOM-TYPE AIR CLEANER DESIGN CRITERIA AND PROTOTYPE PERFORMANCE
Authors:A R McFARLAND  C A Ortiz  D I Dennis JR  R B Bingham
Affiliation:  a Department of Civil Engineering, Air Quality Laboratory, Texas A&M University, College Station, TX b American Plasti-plate Corp., Tyler, TX
Abstract:Two rules-of-thumb for minimum performance of a room-type air cleaner have been developed from consideration of a first order model for room air quality. By adopting a criterion that the use of an air cleaner should cause the particle concentration to be at least cut in half, the rule-of-thumb for a room with no smokers is that the product of filter efficiency and flow rate should be ≥.8 m3/min (≥30 cfm). If the particle concentration is dominated by smokers or other sources, the product of filter efficiency and filter flow rate should be = m3 /min (= 100 cfm)

Tests were conducted to determine the efficiencies of candidate filter media. The selected media, Filtrete G-0115, has a fractional efficiency for 1 μm particles of 97 percent when clean, and an efficiency of 78 percent when fully loaded. This drop in efficiency is due to the masking of the electrets on the surfaces of the filter fibers.

A fibrous filter room-type air cleaner was designed to perform in accordance with the rules-of-thumb. When operated with a clean filter, the maximum flow rate is 3.2 m3/min and, when operated with a fully loaded filter, the maximum flow rate is 1.8 m3/min. The system has a multispeed fan which will provide lower flow rates.
Keywords:
本文献已被 InformaWorld 等数据库收录!
设为首页 | 免责声明 | 关于勤云 | 加入收藏

Copyright©北京勤云科技发展有限公司  京ICP备09084417号