首页 | 本学科首页   官方微博 | 高级检索  
     


Experimental study on fire hazard of typical curtain materials in ISO 9705 fire test room
Authors:Liming Li  Heping Zhang  Qiyuan Xie  Long Chen  Chunming Xu
Affiliation:State Key Laboratory of Fire Science, University of Science and Technology of China, Hefei, Anhui 230027, People's Republic of China
Abstract:Curtain materials are commonly used as decoration, shade, or screen. They are flammable and are usually across a large part of a room, leading to the risk of a high fire hazard. Once ignited, the upward fire spread would accelerate the fire development in an enclosure. In this paper, fire hazard of three typical curtain materials with different pleat rates were tested in an ISO 9705 fire test room. Fire parameters such as temperature field, flame spread rate, heat release rate (HRR), and emitted gases, and the influences of pleat rate and cotton content on flame spread rate were investigated. The correlation between flame spread rate and HRR was discussed. The results show that the upward flame spread has an accelerating rate, and an inverted‐triangle burning area would emerge during the combustion. Some horizontal fibrillar structures appear in this burning area. Pleat rate and cotton content have considerable influence on the curtain fire behavior. The flame spread rate shows a linear response to HRR at the early stage. In addition, a function between average flame spread rate and pleat rate for engineering estimation is proposed, and a linear relationship between HRR/mCO and mmath image/mCO has been obtained. The study results provide valuable reference to building fire simulation and safety design. Copyright © 2011 John Wiley & Sons, Ltd.
Keywords:flame spread rate  heat release rate  pleat rate  cotton content  CO and CO2 concentrations
设为首页 | 免责声明 | 关于勤云 | 加入收藏

Copyright©北京勤云科技发展有限公司  京ICP备09084417号