Particle-triggered pre-breakdown phenomena in atmospheric air gap under AC voltage
Authors:Hara  M Negara  Y Setoguchi  M Kurihara  T Suehiro  J Haashi  N
Affiliation:Graduate Sch. of Inf. Sci. & Electr. Eng., Kyushu Univ., Fukuoka, Japan;
Abstract:Corona discharge mechanism and breakdown voltage characteristics of air gaps in the presence of metallic particles were investigated including the relationship between the corona discharge mechanism and the phase resolved partial discharge patterns. These results are of interest for detection of foreign particles in gas insulated systems (GIS). The results with different shaped particles show that the corona mechanism depends on the particle shape and applied voltage. Moreover the corona discharges on both sides of the particle interfere with each other by inflow of charge carriers into the particle. The breakdown voltage is a minimum when the particle is in the vicinity of the electrode due to active interference of coronas. The phase-charge characteristics as the phase resolved partial discharge patterns vary with the particle shape. This suggests that the corona discharge mechanisms for all types of particles should be considered in the particle-detection method for GIS based on the phase resolved partial discharge patterns.