零值绝缘子误判原因分析及防止措施
引用本文:王卫国.零值绝缘子误判原因分析及防止措施[J].江苏电机工程,2011(5):66-68.
作者姓名:王卫国
作者单位:镇江供电公司;
摘    要:变电站超长串绝缘子测零时,由于分布电压的偏低,可能导致误判.分析了零值绝缘子误判的原因,建议采用测量其分布电压,根据对应的图形来判断绝缘子是否为零值.

关 键 词:变电站  绝缘子  零值

Analysis of Misjudgment of Zero Value Insulator and Countermeasures
WANG Wei-guo.Analysis of Misjudgment of Zero Value Insulator and Countermeasures[J].Jiangsu Electrical Engineering,2011(5):66-68.
Authors:WANG Wei-guo
Affiliation:WANG Wei-guo (Zhenjiang Power Supply Company,Zhenjiang 212001,China)
Abstract:When measuring zero to those long insulator clusters in substations,some of their voltages are misjudged as the distributed voltage is too low.In this paper,the main reasons were analyzed,and some relevant countermeasures were presented.The measurement of distributed voltage was recommended,and whether the voltage is zero or not can be judged from the corresponding graphics.
Keywords:substation  insulator  zero value  