内桥接线变电站中110 kV备自投与10 kV备自投配合研究
引用本文:王静.内桥接线变电站中110 kV备自投与10 kV备自投配合研究[J].四川电力技术,2007,30(1):30-31.
作者姓名:王静
作者单位:成都电业局继保所,四川,成都,610021
摘    要:结合一次实际故障,分析故障发生后110kV进线备投与10kV桥备投的动作情况,得出两种备自投如何配合的结论:关键在于合理整定10kV桥备投放电延时,使得110kV进线备投动作过程中不对10kV桥备投放电,避免扩大停电范围。

关 键 词:进线备投  桥备投  内桥接线
文章编号:1003-6954(2007)01-0030-02
修稿时间:2006-09-02

Analysis of Cooperation Problem between 110kV and 10kV Backup Self- switching Equipment in Substation with Internal Bridge Connection
Wang Jing.Analysis of Cooperation Problem between 110kV and 10kV Backup Self- switching Equipment in Substation with Internal Bridge Connection[J].Sichuan Electric Power Technology,2007,30(1):30-31.
Authors:Wang Jing
Abstract:The actions of 110kV backup self- switching equipment and 10kV backup self- switching equipment after a fault are analyzed, and a conclusion about the cooperation between these two backup self- switching equipments is obtained. The discharge delay of lOkV backup self-switching equipment must be reasonably set, so that 10kV backup self-switching equipment cannot be discharged in the course of the actions of llOkV backup self- switching equipment, and it can avoid the extension of power interruption.
Keywords:llne backup self- switching equipment  bridge backup self- switching equipment  internal bridge connection