一起110kV线路零序方向保护误动原因分析
引用本文:王薇,肖敏,王国江.一起110kV线路零序方向保护误动原因分析[J].高压电器,2010,46(7).
作者姓名:王薇  肖敏  王国江
作者单位:西安供电局,陕西,西安,710032
摘    要:针对一起110kV线路零序方向保护误动导致4个变电站失压的事故,结合故障录波图和保护动作报告,通过理论分析,指出事故原因在于同杆架设的平行线路零序互感对零序方向保护产生影响和变压器中性点非正常接地,并提出了解决措施。

关 键 词:零序方向保护  误动  同杆线路  零序互感

Analysis of a Mal-operation of Zero Sequence Directional Protection on 110 kV Transmission Line
WANG Wei,XIAO Min,WANG Guo-jiang.Analysis of a Mal-operation of Zero Sequence Directional Protection on 110 kV Transmission Line[J].High Voltage Apparatus,2010,46(7).
Authors:WANG Wei  XIAO Min  WANG Guo-jiang
Abstract:A mal-operation of zero sequence directional protection on 110 kV transmission line caused four substations losing their voltage. This paper analyzes this fault theoretically by combining the recorded fault waveforms and protection operation reports,and discovers that this mal-operation was caused by abnormal ground of a transformer neutral and by the effect of zero sequence mutual inductance of parallel transmission lines on zero sequence directional protection. Solutions are offered to eliminate this kind of fault.
Keywords:zero sequence directional protection  mal-operation  parallel lines  zero sequence mutual inductance