首页 | 本学科首页   官方微博 | 高级检索  
     


Condensation in a vertical tube bundle passive condenser – Part 2: Complete condensation
Authors:Gavin Henderson  Wenzhong Zhou  Shripad T Revankar
Affiliation:1. Korea Atomic Energy Research Institute (KAERI), Innovative System Safety Research Division, Daedeok-daero 989-111, Yuseong-gu, Daejeon 34057, Republic of Korea;2. Korea Advanced Institute of Science and Technology (KAIST), Department of Nuclear and Quantum Engineering, Daehak-ro 291, Yuseong-gu, Daejeon 34141, Republic of Korea;1. Japan Aerospace Exploration Agency, 2-1-1 Sengen, Tsukuba, Ibaraki 305-8505, Japan;2. Institute of Fluid Science, Tohoku University, 2-1-1 Katahira, Aoba-ku, Sendai, Miyagi 980-8577, Japan;3. Department of Aerospace Engineering, Tohoku University, 6-6-1 Aoba, Aramaki, Aoba-ku, Sendai, Miyagi 980-8579, Japan
Abstract:An experimental study of the tube bundle effect on heat removal capabilities in complete condensation mode of a passive condenser was performed. A full scale test section, with four condenser tubes, was designed and constructed to simulate operating conditions of a passive containment cooling system. For complete condensation analysis, pure steam was supplied to the test section and heat transfer properties were measured for pressure from 100 to 280 kPa. The condensation heat transfer results were similar to the findings from single tubes, except for a slightly higher condensate mass flux. This was determined to be a result of turbulent mixing in the secondary boiling water caused by the tube bundle.
Keywords:
本文献已被 ScienceDirect 等数据库收录!
设为首页 | 免责声明 | 关于勤云 | 加入收藏

Copyright©北京勤云科技发展有限公司  京ICP备09084417号