首页 | 本学科首页   官方微博 | 高级检索  
     

某电站3号主变压器故障诊断分析及处理
引用本文:范青川.某电站3号主变压器故障诊断分析及处理[J].青海电力,2014,33(3):48-50.
作者姓名:范青川
作者单位:黄河电力检修工程有限公司,青海西宁,810016
摘    要:龙羊峡3号主变压器投运后多次出现裸金属过热故障,通过对变压器投运初期低负荷和大负荷运行时色谱分析,结合历次排油检查、吊罩检修、返厂维修、红外测温和接地电流测试情况,确定了变压器磁路故障是引起裸金属过热的主要原因,并提出了相应措施。

关 键 词:变压器  色谱分析  金属过热

Analysis on the No.3 Main Transformer Fault in a Power Generation Station and Treatment
FAN Qingchuan.Analysis on the No.3 Main Transformer Fault in a Power Generation Station and Treatment[J].Qinghai Electric Power,2014,33(3):48-50.
Authors:FAN Qingchuan
Affiliation:FAN Qingchuan
Abstract:After being put in service, the No. 3 main transformer of the Longyangxia hydropower station experienced bare metal overheating faults. This paper, based the chromatographic analysis during initial stage with low load and high load, analyzes information from check, repairs and tests, concludes that the transformer magnet path fault is the primary cause of the bare metal overheating faults. Finally this paper gives improvement measures.
Keywords:transformer  chromatographic analysis  metal overheating