作者单位:浙江龙驰防腐技术有限公司,浙江宁波,315000
摘    要:10kV电机起动后,当电流下降至1.5倍额定电流及综保设定时间满足(如40s),短接柜切除热变电阻软起动器,此时电机投全压,起动过程结束。本文扼要介绍其工作原理,并对两起起动失败案例进行分析与探讨。

关 键 词:软起动器  10kV电机  故障分析  短接柜

The Malfunction Analyze and Discussion of Running Cabinet and Shorting Cabinet when 10kV Motor Starting
Shi Haiqin.The Malfunction Analyze and Discussion of Running Cabinet and Shorting Cabinet when 10kV Motor Starting[J].Electrical Engineering,2011(12):71-73.
Authors:Shi Haiqin
Affiliation:Shi Haiqin(Zhejiang Lognkey Corrosion Control Technonoly Co.,Ltd,Ningbo,Zhejiang 315000)
Abstract:After 10kV motor starts,its current decreases to 1.5Ie(Ie: rated current),and the set time arrives(I.E.40second),shorting cabinet cuts our HTR(high voltage temperature resistor soft starter),the motor gets the full voltage.Then the starting is the end.This paper introduces its working principle simply,and analyzes,discuss the two failure starts.
Keywords:Soft-starter  10kV motor  malfunction analyze  shorting cabinet