10kV干式空心串联电抗器故障原因分析
引用本文:李阳林,万军彪,黄瑛.10kV干式空心串联电抗器故障原因分析[J].电力电容器,2011(3):58-61.
作者姓名:李阳林  万军彪  黄瑛
作者单位:江西省电力科学研究院;
摘    要:通过对江西省连续发生的2起干式空心串联电抗器故障原因的分析,发现铝材料的不均匀、绝缘材料的耐热等级偏低以及并联电容器组的频繁操作导致了这2起故障的发生。由此,向运行维护部门提出了故障防范措施。

关 键 词:电抗器  局部过热  耐热等级

Fault Analysis on 10 kV Dry-type Air-core Series Reactor
LI Yang-lin,WAN Jun-biao,HUANG Ying.Fault Analysis on 10 kV Dry-type Air-core Series Reactor[J].Power Capacitors,2011(3):58-61.
Authors:LI Yang-lin  WAN Jun-biao  HUANG Ying
Affiliation:LI Yang-lin,WAN Jun-biao,HUANG Ying (Jiangxi Provincial Electric Power Scientific Research Institute,Nanchang 330096,China)
Abstract:From the analysis of two consecutive faults of dry-type air-core series reactor in Jiangxi Province,it is found that those two faults are caused by the unevenness of aluminum,low thermal insulation class of insulating materials and frequent operations of shunt capacitor banks.Accordingly,precautionary measures are proposed for the operation and maintenance department.
Keywords:reactor  partial overheating  thermal insulation grade  