首页 | 本学科首页   官方微博 | 高级检索  
     

特高压变电站工频电磁场对避雷器在线监测装置测量准确度影响研究
引用本文:张露,王永勤,贺家慧,吴彤,罗浪,李佳,张兴无. 特高压变电站工频电磁场对避雷器在线监测装置测量准确度影响研究[J]. 电力系统保护与控制, 2018, 46(3): 164-169
作者姓名:张露  王永勤  贺家慧  吴彤  罗浪  李佳  张兴无
作者单位:国网湖北省电力有限公司电力科学研究院,湖北 武汉 430071,国网湖北省电力有限公司电力科学研究院,湖北 武汉 430071,国网湖北省电力有限公司电力科学研究院,湖北 武汉 430071,国网湖北省电力有限公司电力科学研究院,湖北 武汉 430071,国网湖北省电力有限公司检修公司,湖北 武汉 430050,国网湖北省电力有限公司检修公司,湖北 武汉 430050,国网湖北省电力有限公司检修公司,湖北 武汉 430050
摘    要:变电站现场存在各种干扰,可能影响避雷器泄漏电流的测量准确度。在实验室内对避雷器在线监测装置开展试验,施加工频电场/工频磁场干扰并检验测量准确度。在工频电场干扰时,若传感器电流线未采用屏蔽,泄漏电流测量读数会出现较明显的波动。传感器电流线采用屏蔽能够有效抵制工频电场干扰布线方式的改变,也会明显改变避雷器泄漏电流的测量结果。在工频磁场增大的情况下,避雷器泄漏电流的波动范围也会增大。

关 键 词:工频电磁场干扰;避雷器;泄漏电流;在线监测装置;测量准确度

Accuracy examination of linkage current online measurement of surge arresters under power frequency interference of electric field and magnetic field in the ultra-high voltage substations
ZHANG Lu,WANG Yongqin,HE Jiahui,WU Tong,LUO Lang,LI Jia and ZHANG Xingwu. Accuracy examination of linkage current online measurement of surge arresters under power frequency interference of electric field and magnetic field in the ultra-high voltage substations[J]. Power System Protection and Control, 2018, 46(3): 164-169
Authors:ZHANG Lu  WANG Yongqin  HE Jiahui  WU Tong  LUO Lang  LI Jia  ZHANG Xingwu
Affiliation:Electric Power Research Institute of State Grid Hubei Electric Power Corporation Ltd, Wuhan 430071, China,Electric Power Research Institute of State Grid Hubei Electric Power Corporation Ltd, Wuhan 430071, China,Electric Power Research Institute of State Grid Hubei Electric Power Corporation Ltd, Wuhan 430071, China,Electric Power Research Institute of State Grid Hubei Electric Power Corporation Ltd, Wuhan 430071, China,Maintenance Company of State Grid Hubei Electric Power Corporation Ltd, Wuhan 430050, China,Maintenance Company of State Grid Hubei Electric Power Corporation Ltd, Wuhan 430050, China and Maintenance Company of State Grid Hubei Electric Power Corporation Ltd, Wuhan 430050, China
Abstract:Various kinds of interference in the ultra-high voltage substations are significantly inferential to the linkage current measurement of surge arresters. In order to check the normal measurement of the linkage online current measurement of surge arresters, both electric field and magnetic field interference at power frequency is proposed in the lab tests. Under the electric field interference, the test results of linkage current are over the error of the nominal value on the plate of the device if the wires of the sensor are not shielded. However, using the shielding can avoid this electric field interference. Moreover, placement of the wires can obviously change the measurement results. Meanwhile, the level of change of the measurement data increases with the electric field interference.
Keywords:electromagnetic interference at power frequency   surge arrester   leakage current   online measuring device   measurement accuracy