首页 | 本学科首页   官方微博 | 高级检索  
     

直流分量电流作CV电缆老化诊断方法的现场运用探讨
引用本文:邱为平.直流分量电流作CV电缆老化诊断方法的现场运用探讨[J].四川电力技术,1994(5).
作者姓名:邱为平
摘    要:介绍在实际敷设电缆时如何有效消除杂散电流以期提高直流分量电流进行CV电缆老化监测的测试精度。

关 键 词:绝缘监测,直流分量,水树枝,CV电缆,杂散电流

Application of On-Line Diagnoses for XLPE Cables by DC Component Method to On-Site Installed Cables
Atsushi Iga, Tatsuki Okamoto Naohiro Hozumi, Seiji Sasaki.Application of On-Line Diagnoses for XLPE Cables by DC Component Method to On-Site Installed Cables[J].Sichuan Electric Power Technology,1994(5).
Authors:Atsushi Iga  Tatsuki Okamoto Naohiro Hozumi  Seiji Sasaki
Affiliation:Atsushi Iga; Tatsuki Okamoto Naohiro Hozumi; Seiji Sasaki
Abstract:The water tree diagnoses of 6. 6kV class XLPE cables by DC component method are described. This method measures the DC current component by energizing the cable with AC high voltage, therefore it would be suitable for on-line diagnoses. The DC component is considered to appear due to the rectifying effect of water trees inside the insulation.In the laboratory test, the DC component showed a good correlation with the degradation. However, almost no correlation was seen in the on-site measurement. The cause of this bad correlation found by the authors is galvanic effect inside the jacket. The jacket resistivity being low, this generates the noise current through the grounding circuit. Based on this finding, the equivalent circuit of on site measurement wes proposed.Considering the equivalent circuit, two methods were proposed to discriminate the true DC component out of noise current. One is to by-pass the noise current from the measurement apparatus, and the other is to statistically estimate the true DC component by using the transition in the jacket resistivity.The on-site test were carried out to confirm the applicability of these methods.
Keywords:insulation monitoring DC component water tree CV cable stray current  
本文献已被 CNKI 等数据库收录!
设为首页 | 免责声明 | 关于勤云 | 加入收藏

Copyright©北京勤云科技发展有限公司  京ICP备09084417号