首页 | 本学科首页   官方微博 | 高级检索  
     


New absorption chiller and control strategy for the solar assisted cooling system at the German federal environment agency
Affiliation:1. Department of Mechanical Engineering, Universitat Rovira i Virgili, CREVER Avda Paisos Catalans, 26, 43007 Tarragona, Spain;2. Department of Mechanical Engineering, College of Engineering, Guindy, Anna University, Chennai, Tamil Nadu 600 025, India
Abstract:Typically the cooling capacity of absorption chillers is controlled by adjusting the driving hot water temperature according to the load. Meanwhile the cooling water temperature is controlled to a constant set value. In order to increase the solar cooling fraction and/or to decrease the operating costs of solar assisted cooling systems (SAC-systems) a new control strategy has been developed which controls hot and cooling water temperature simultaneously. Hereby the specific cost of cold – generated from solar or conventional heat – can be reduced. The basic concept of the strategy is explained and results are shown for the SAC-system at the Federal Environment Agency in Dessau, Germany. Here a recently developed absorption chiller is now used instead of a former adsorption chiller. With the new absorption chiller and the control strategy the seasonal energy efficiency ratio SEER is above 0.75, electric efficiency is 35% higher and water consumption is reduced by 70%.
Keywords:Absorption chiller  Adsorption chiller  Monitoring  Control strategy  Cold price  Refroidisseur à absorption  Refroidisseur à adsorption  Surveillance  Prix du froid  Stratégie de régulation
本文献已被 ScienceDirect 等数据库收录!
设为首页 | 免责声明 | 关于勤云 | 加入收藏