首页 | 本学科首页   官方微博 | 高级检索  
     


Application of two‐loop robust control to air‐conditioning systems
Authors:Gongsheng Huang  Arthur L Dexter  Shengwei Wang
Affiliation:1. Division of Building Science & Technology, City University of Hong Kong, Kowloon, Hong Kong;2. Department of Engineering Science, University of Oxford, Parks Road, Oxford OX1 3PJ, United Kingdom;3. Department of Building Services Engineering, Hong Kong Polytechnic University, Kowloon, Hong Kong
Abstract:This paper presents the design and application of a two‐loop robust controller for temperature control in air‐conditioning systems. A Takagi‐Sugeno fuzzy model with uncertain local models is developed to describe the associated nonlinearities and uncertainties in the operation of the air handling units. Parallel distributed compensation is used to design the global control law. The local control law consists of two loops: an inner‐loop integral controller and an outer‐loop min‐max predictive controller with short prediction horizon. A discounting scheme is developed to weight the contribution of the two loops. Experimental results are presented which show that the proposed strategy can achieve acceptable control performance with a minimum of onsite tuning. Copyright © 2009 John Wiley and Sons Asia Pte Ltd and Chinese Automatic Control Society
Keywords:Robust control  controller design  Takagi‐Sugeno fuzzy model  air‐conditioning system
设为首页 | 免责声明 | 关于勤云 | 加入收藏

Copyright©北京勤云科技发展有限公司  京ICP备09084417号