Seasonal cooling performance of a ground-coupled heat pump system in a hot and arid climate
Authors:Mustafa &#x  nall&#x  ,Hikmet Esen
Affiliation:aDepartment of Mechanical Engineering, Faculty of Engineering, Fırat University, 23119 Elazığ, Turkey;bDepartment of Mechanical Education, Faculty of Technical Education, Fırat University, 23119 Elazığ, Turkey
Abstract:The goal of the present study is to validate the cooling performance of a ground-coupled heat pump system established in Fırat University, Elazığ (38.41°N, 39.14°E), Turkey. The cooling load of the test room was 3.1 kW at design conditions. The experimental results were obtained from June to September in cooling season of 2003. The ground heat exchanger was used, and it was buried with in 2 m depth trench. The average cooling performance coefficient of the system (COPoverall) was obtained to be 2.01. The results obtained from experimental measurement showed that these systems could be used safely, reliably and efficiently at the lowest possible cost for Elazığ, Turkey climatic conditions. Especially, the seasonal energy efficiency ratio (SEER) of this system is moderate at longer-term testing.
Keywords:Ground-coupled heat pump   Space cooling   Horizontal heat exchanger   Coefficient of performance