宝珠寺电厂3 W定子接地保护动作的原因分析处理
引用本文:邓凤琼,康永刚,聂铤. 宝珠寺电厂3 W定子接地保护动作的原因分析处理[J]. 四川水力发电, 2007, 26(3): 37-38
作者姓名:邓凤琼  康永刚  聂铤
作者单位:华电四川宝珠寺水力发电厂,四川,广元628003;国电南自凌伊电力自动化有限公司,江苏,南京210013
摘    要:针对宝珠寺电站2号机3W定子接地保护动作的情况,对其原因进行了分析和查找,发现是由于PT柜内的A相二次保险接触不良造成的。通过更换二次保险的卡座后装置恢复正常运行。

关 键 词:3W定子接地保护  动作  检查分析与处理  二次保险接触不良  宝珠寺电厂
文章编号:1001-2184(2007)03-0037-02
修稿时间:2007-04-20

Case Study on 3W Stator Ground Protection Action at Baozhusi Hydropower Plant
DENG Feng-qiong,KANG Yong-gang,NIE Ting. Case Study on 3W Stator Ground Protection Action at Baozhusi Hydropower Plant[J]. Sichuan Water Power, 2007, 26(3): 37-38
Authors:DENG Feng-qiong  KANG Yong-gang  NIE Ting
Abstract:The causes for 3W stator ground protection action are studied and looked for in No.2 unit at Baozhusi Hydropower Plant.It is found that this is caused by poor connection of A phase secondary safety device in PT block.The device operates normally after bayonet socket of the secondary safety device is changed.
Keywords:3W stator ground protection  action  check  analysis and treatment  poor connection of secondary safety device  Baozhusi Hydropower Plant