地源热泵系统热短路分析
引用本文:杨卫国,王京.地源热泵系统热短路分析[J].房材与应用,2008(2):12-14.
作者姓名:杨卫国  王京
作者单位:邯郸职业技术学院,河北邯郸056001
摘    要:主要进行地源热泵系统的热短路实验研究,对河北工程大学120m埋深地源热泵U型埋管实验室进行冬季性能测试,进行多流量工况的测试,流量分别为4t/h、3.5t/h、3t/h各运行5d,地下埋管单位井深换热量也会随着流量的减小而减少;埋管中的流量变化和埋管中的换热量的大小对热短路都有影响。通过热短路分析,提出了改进措施。

关 键 词:热短路  地源热泵  U型埋管换热器  单位井深换热量
文章编号:1673-7237(2008)02-0012-03
收稿时间:2007-08-05
修稿时间:2007-10-17

Thermal Short-circuiting Analysis on Groud Source Heat Pump
YANG Wei-guo, WANG Jing.Thermal Short-circuiting Analysis on Groud Source Heat Pump[J].Housing Materials & Applications,2008(2):12-14.
Authors:YANG Wei-guo  WANG Jing
Abstract:Thermal short-circuiting of the source heat pump system was studied. 120 metres U-tube underground heat exchanger perfor-mance of Hebei Engineering University in winter was tested. Multi-flow tests of 4t/h, 3.5t/h and 3t/h of respective five-day operation were discussed. Heat exchange quantity of per well depth can reduce along with the reduction of the current flow, and some influences of the flow change and the heat exchanger in the tube of underground on thermal short-circuiting were described. To analyze the thermal short-circuiting, some improvement measures were put forward.
Keywords:thermal short-circuiting  ground source heat pump  U-tube underground heat exchanger  heat exchange quantity of per well depth