首页 | 本学科首页   官方微博 | 高级检索  
     


The fluorinated olefin R-1234ze(Z) as a high-temperature heat pumping refrigerant
Authors:J. Steven Brown   Claudio Zilio  Alberto Cavallini
Affiliation:aDepartment of Mechanical Engineering, Catholic University of America, 620 Michigan Ave., NE, Washington, DC 20064, USA;bDipartimento di Fisica Tecnica, Università di Padova, Padova, 35131, Italy
Abstract:Estimates are provided for R-1234ze(Z) of its: (1) critical temperature, pressure, and density, acentric factor, and ideal gas specific heat at constant pressure, and (2) various thermodynamic and transport properties, which are used to predict the performance potential of R-1234ze(Z) in high-temperature heat pumping applications. In particular, for an idealized cycle, the coefficient of performance and volumetric heating capacity for R-114 are 3.24 and 1667 kW m−3, respectively, and for R-1234ze(Z) are 3.40 and 1645 kW m−3, respectively. The attractiveness of R-1234ze(Z) is confirmed further through heat exchanger simulations. This paper demonstrates that R-1234ze(Z) deserves further consideration as a possible R-114 replacement.
Keywords:Heat pump   Refrigerant   Review   R-1234ze(Z)   Thermodynamic propertyMots clé  s: Pompe à   chaleur   Frigorigè  ne   Enquê  te   R-1234ze(Z)   Proprié     thermodynamique
本文献已被 ScienceDirect 等数据库收录!