Sensitivity studies on power transformer ferroresonance of a 400 kV double circuit
Authors:Charalambous   C. Wang   Z.D. Osborne   M. Jarman   P.
Affiliation:Sch. of Electr. & Electron. Eng., Univ. of Manchester, Manchester;
Abstract:The ability to predict ferroresonance significantly relies on the accuracy of the transformer model and the power system's parameters. The accomplishment of a suitable simulation model allows the sensitivity studies to be performed to determine the degree of influence of various components and parameters of the ferroresonance phenomenon such as line length, point-on-wave switching and transformer core loss. The modelling work carried out in ATP (commercially available software) on a 1000 MVA 400/275/13 kV power transformer model is described and the simulation with field ferroresonance test recordings is verified. The maps that define the boundaries between safe and ferroresonant (fundamental, subharmonic, chaotic) regions as a function of system parameters are created through the sensitivity studies performed.
Keywords: