交直流型微电网中光伏逆变器并联控制策略
引用本文:袁建华,高厚磊,高峰,吴疆,刘博,季笑庆,王云波. 交直流型微电网中光伏逆变器并联控制策略[J]. 电网技术, 2012, 0(8): 19-23
作者姓名:袁建华  高厚磊  高峰  吴疆  刘博  季笑庆  王云波
作者单位:1. 三峡大学电气与新能源学院,湖北省宜昌市443002
2. 山东大学电气工程学院,山东省济南市250061
3. 烟台供电公司,山东省烟台市264001
基金项目:山东省科技攻关项目(210GGX10706);山东电力集团公司科技项目支持课题(2010A-61)
摘    要:针对光伏电源和储能装置主要配置在直流网,交流网在离网时需克服光伏电源出力波动的问题,提出一种微电网离网模式下的光伏逆变器并联控制策略:直流网侧逆变器为主逆变器,采用恒定电压幅值以及 P-f 下垂法为交流网提供全部无功及部分有功功率;少数较小容量的光伏逆变器为从逆变器,从逆变器不提供无功,采用自适应下垂系数法输出与实时最大功率匹配的有功功率,既维持交流网电压稳定,又充分利用光伏发电.基于 MATLAB 的系统模型仿真证明了该方法的正确性与可行性.

关 键 词:交直流  微电网  光伏逆变器  控制策略  最大功率

An Adaptive Control Strategy for Parallel Inverters of Hybrid DC/AC PV Micro-Grid
YUAN Jianhua,GAO Houlei,GAO Feng,WU Jiang,LIU Bo,JI Xiaoqing,WANG Yunbo. An Adaptive Control Strategy for Parallel Inverters of Hybrid DC/AC PV Micro-Grid[J]. Power System Technology, 2012, 0(8): 19-23
Authors:YUAN Jianhua  GAO Houlei  GAO Feng  WU Jiang  LIU Bo  JI Xiaoqing  WANG Yunbo
Affiliation:1.School of Electrical Engineering & Renewable Energy,China Three Gorges University,Yichang 443002,Hubei Province,China; 2.School of Electrical Engineering,Shandong University,Jinan 250061,Shandong Province,China; 3.Yantai Power Supply Company,Yantai 264001,Shandong Province,China)
Abstract:Photo voltaic(PV) generation and energy storage devices are mainly configured in sub DC network of hybrid AC/DC microgrid and provide power supply for DC load,and using parallel PV inverters a part of PV generations can be connected with sub AC network via point of common coupling(PCC) to supply power for AC loads,thus when sub AC network is being disconnected from conventional power grid the fluctuation of power output of PV generation in sub AC network should be eliminated.A control strategy for parallel PV inverters under the condition of disconnecting sub AC network from conventional grid was proposed:the parallel PV inverter configured in DC network was regarded as master inverter and supply total reactive power and part of active power for sub AC network by constant voltage amplitude and power-frequency droop method;a part of PV inverters with lower capacities were regarded as slave inverters,which did not supply reactive power and supplied only active power controlled by adaptive droop coefficient method,and this part of active power was matched with maximum real-time power of PV generation,thus not only the voltage stability of sub AC network could be maintained,but also the capabilities of PV generations could be fully utilized.Both correctness and feasibility of the proposed control strategy were verified by results of simulation based on Matlab.
Keywords:DC/AC  micro-grid  photo voltaic(PV) inverter  control strategy  maximum power