首页 | 本学科首页   官方微博 | 高级检索  
     


Simultaneous ultrawide and narrowband detection of PD pulses indielectric liquids
Authors:Pompili  M Mazzetti  C Bartnikas  R
Affiliation:Dept. of Electr. Eng., Rome Univ.;
Abstract:Simultaneous narrow band (300 kHz) and wide band (500 MHz) measurements were carried out to obtain estimates of the apparent charge transfer associated with discrete isolated discharge pulses and discharge pulse bursts, which are observed to occur in dielectric liquids when wide band detection systems are utilized. The integrated apparent charge transfers determined with the narrow band system ranged from 12 to 95 pC, which represents typically the lower range of values normally encountered with PD activity in dielectric liquid-filled or impregnated equipment. While the discharge phenomena in perfluoro polyether liquids was found to be typified by sporadic appearances of single isolated pulses involving charge transfers between 33 and 38 pC, the discharge events in mineral oils assumed most frequently the form of pulse bursts, displaying the usual pulse sequences of quasi-ascending amplitudes; the overall integrated apparent charge transfer of the observed pulse bursts extended commonly from 12 to 16 pC. The charge release, occurring with the first (initiating) smallest discharge pulse within the pulse bursts, was estimated to be of the order of ~1 pC
Keywords: