550 kV GIS变电站中VFTO仿真计算及抑制措施
引用本文:贺天任,高宇,刘晓航,张瑞.550 kV GIS变电站中VFTO仿真计算及抑制措施[J].电力系统及其自动化学报,2022,34(2):65-70,81.
作者姓名:贺天任  高宇  刘晓航  张瑞
作者单位:天津大学电气自动化与信息工程学院,天津 300072;深圳供电局有限公司,深圳 518000,天津大学电气自动化与信息工程学院,天津 300072,天津大学电气自动化与信息工程学院,天津 300072;国网辽宁省电力有限公司,铁岭 112000,天津大学电气自动化与信息工程学院,天津 300072;国网山东省电力公司,济宁 272200
摘    要:在气体绝缘变电站GIS(gas insulated substation)中,隔离开关进行分合母线时引起的特快速暂态过电压VFTO(very fast transient overvoltage)威胁站内设备安全,深入认识VFTO的特点并提出适当的抑制措施对于保障GIS变电站的安全具有重要意义.选取深圳某550 kV ...

关 键 词:气体绝缘变电站  特快速暂态过电压  抑制措施  阻波器  铁氧体磁环

Numerical Simulation and Suppression Measure for VFTO in 550 kV GIS Substation
HE Tianren,GAO Yu,LIU Xiaohang,ZHANG Rui.Numerical Simulation and Suppression Measure for VFTO in 550 kV GIS Substation[J].Proceedings of the CSU-EPSA,2022,34(2):65-70,81.
Authors:HE Tianren  GAO Yu  LIU Xiaohang  ZHANG Rui
Affiliation:(School of Electrical and Information Engineering,Tianjin University,Tianjin 300072,China;Shenzhen Power Supply Bureau Co.,Ltd,Shenzhen 518000,China;State Grid Liaoning Electric Power Co.,Ltd,Tieling 112000,China;State Grid Shandong Electric Power Company,Jining 272200,China)
Abstract:In a gas insulated substation(GIS),the very fast transient overvoltage(VFTO)caused by opening and clos?ing the isolating switch of a busbar threatens the safety of the equipment in the station.Therefore,it is of significance for ensuring the safety of the GIS substation through understanding the characteristics of VFTO and further proposing ap?propriate suppression measures.In this paper,a 550 kV GIS substation in Shenzhen is taken as the research object,and electro-magnetic transient program/alternative transient program(EMTP/ATP)is used to simulate the VFTO gener?ation process and its characteristics as the isolating switch is connected to the busbar.The influences of transformer in?let capacitance and the length of transformer incoming line on the VFTO waveform,amplitude and frequency are ana?lyzed,and the methods for suppressing VFTO by means of a wave trap and ferrite magnetic ring are proposed.Results show that with the increase in transformer inlet capacitance,the amplitude of VFTO increases.When the length of the transformer incoming line increases,the frequency of VFTO decreases.Moreover,the wave trap has a better VFTO sup?pression effect than the ferrite magnetic ring.The conclusions drawn from this paper are helpful for the prevention and control of VFTO in GIS substations.
Keywords:gas insulated substation(GIS)  very fast transient overvoltage(VFTO)  suppression measure  wave trap  ferrite magnetic ring